Symptoms: PDU Reporting Overload Warning¶
- The monitoring system fires a critical alert: PDU-A in rack C14 reports 87% load (34.8A on a 40A circuit).
- The PDU is a ServerTech Switched CDU, 208V 3-phase, 40A per phase.
- Phase L2 is the one overloaded; phases L1 (22.1A, 55%) and L3 (24.6A, 62%) are within normal range.
- The alert threshold is 80% (32A); the warning threshold is 70% (28A).
- The rack contains a mix of 1U and 2U servers plus two top-of-rack switches.
- Two new GPU-accelerated servers (2U, dual PSU) were installed in the rack yesterday.
- PDU-B (redundant feed) shows similar imbalance: L2 at 78%.
- The facility team confirms the branch circuit breaker has not tripped but is warm to the touch.
- No servers are currently experiencing power issues, but a breaker trip would be catastrophic.